The MAIB  has issued a warning about condensed aerosol fire extinguishing system after fatality on MV ‘Resurgam’ PZ 1001

The Marine Accident Investigation Board (MAIB) has issued a bulletin to fishing vessel owners after a fatal accident on board the ‘Resurgam’ PZ 1001 on the 15 November 2019.

The fatality occurred after the inadvertent discharge of a FirePro condensed aerosol fire extinguishing system during its installation on board the fishing vessel.

The report has found that inhalation of a high concentration of the suppressant particles from the discharge could significantly contribute to a fatality. 

The MAIB is carrying out an investigation into the fatality of a shore-based engineering apprentice who was working in the engine room of the ‘Resurgam’ in Newlyn on 15 November 2019. 

The MAIB will publish a full report on completion of the investigation. Andrew Moll Chief Inspector of Marine Accidents.

The MAIB has though published the background pertaining to the investigation and the incident that occurred that fateful day:

On 15 November 2019, the UK registered fishing vessel ‘Resurgam’ was in Newlyn, England undergoing maintenance. 

An engineer and an apprentice from the owner’s shore-based support team were working on the main engine in the engine room. Also working in the engine room were two contractors installing a new FirePro condensed aerosol fire extinguishing system. 

During the installation and without warning, the fire extinguishing system partially and inadvertently discharged, filling the engine room with a dense cloud of aerosol fire suppressing particles (Figure 1). 

Both installation contractors and the company’s engineer managed to evacuate, but the apprentice collapsed in the engine room.

Fig. 1 – Typical discharge of a condensed aerosol fire suppressant (not at time of accident) Aerosol generator

He was later recovered by the local fire and rescue service but was found not breathing and could not be resuscitated. 

INITIAL FINDING

 The exact causes and circumstances of this accident are still being investigated and the findings will be published by the MAIB in a full investigation report.

However, during the inadvertent discharge, it is evident that the apprentice inhaled a high concentration of the suppressant particles and this significantly contributed to the fatality. 

FirePro’s Installation and User Manual and its product’s material safety data sheets had recognised the inadvertent discharge of the system, particularly during installation and maintenance, as a hazard. 

However, the loss of life was not identified as a potential outcome; therefore, the risk associated with inhaling or ingesting a large volume of the suppressant particles was not fully appreciated or protected against.

 SAFETY LESSONS 

Vessel owners, operators and those contracted to install FirePro and other similar condensed aerosol fire extinguishing systems should be fully aware of the potential risk to life from exposure to the aerosol particles. 

Safety precautions should be put in place to ensure that personnel are not exposed to this hazard:

  • Prior to intentional discharge of a condensed aerosol system, there should be visible and audible alarms to alert personnel. Checks should also be made to ensure the protected compartment has been evacuated before the system is activated.
  • When condensed aerosol fire extinguishing systems are being installed or maintained the system should be fully isolated to guard against inadvertent activation, non-essential personnel should be clear of the area and an enclosed space rescue plan should be in place. RECOMMENDATION FirePro is recommended to: S2020/114 Issue a safety alert to the owner/operators of vessels fitted with its systems and its network of marine installation/maintenance engineers highlighting the circumstances of this accident and advising them of appropriate measures to take to reduce the risk of exposure to fire suppressant particles. Safety recommendations shall in no case create a presumption of blame or liability

Source Marine Accident Investigation Board

 

 

 